This field contains the block identification code of 9901 for the
block.
This field defines the number of CROB blocks to generate.
The valid range for the field is 1 to 6.
Data for the command relay block (CROB) to be generated.
Data for the command relay block (CROB) to be generated.
Data for the command relay block (CROB) to be generated.
Data for the command relay block (CROB) to be generated.
Data for the command relay block (CROB) to be generated.
The 10-word data area for each command is defined in the following table.
Clear 3rd bit to disable. Set 5th bit to select IED DB for write
functions
IED node address for the server to consider on the network.
Function codes 3 (select/operate), 5 (direct operate with ACK),
and 6 (direct operate no ACK) supported. Function code 4 is
automatically sent after a successful function 3.
Point in IED to consider with the CROB.
This is a standard DNPNET protocol control code byte (see
description below).
This parameter specifies the number of pulses to generate for
pulse output control. This parameter has a range of 0 to 255
as the value is a byte parameter in the CROB. If a value of
zero is entered, the operation will not execute.
This parameter specifies the on-time interval for pulse control.
This parameter specifies the off-time interval for pulse control.
The control code in the command is a bit-coded byte value with the following definition:
These bits determine the control operation to be performed by
the command: 0=No operation, 1=Pulse on, 2=Pulse off,
3=Latch on and 4=Latch off. All other values are undefined in
the DNPNET protocol.
0=Normal (execute once), 1=Re-queue (place at end of queue
after operation).