Contents MVI56E-DNPNET ♦ ControlLogix Platform
User Manual DNPNET Ethernet Client/Server Communication Module
Page 100 of 140 ProSoft Technology, Inc.
February 13, 2015
This field is used to hold the sequence counter for each 9959
block transfer. This is used to synchronize and confirm receipt
of the block by the module.
This is the data point in the DNPNET analog input database
represented by the event.
Regardless of the Class defined for the given point number,
this will be the Class of the event. (1, 2, or 3)
Value of the point. 16-bit integer, 32-bit integer, or 32-bit float
can be packed into this space
Year of the event timestamp
Month of the event timestamp
Day of the event timestamp
Hour of the event timestamp
Minute of the event timestamp
Seconds of the event timestamp
Milliseconds of the event timestamp
Ten words of data for Event #2
Ten words of data for Event #20
Up to 20 events can be passed from the ControlLogix processor to the module in each
block. To insure that the block reached the module and was processed, the module will
send a response read block 9959 to the ControlLogix processor.
Block identification code for request from PLC by the module.
This field contains the number of events processed/received
by the module.
Sequence
Counter Received
Sequence counter Received for each block transfer, used to
synchronize and confirm receipt of the block by the module.
This field contains the sequence counter of the last successful
block 9959 received.
Identification code for block set to 9959.
Comentários a estes Manuais