Contents MVI56E-DNPNET ControlLogix Platform
User Manual DNPNET Ethernet Client/Server Communication Module
Page 124 of 140 ProSoft Technology, Inc.
February 13, 2015
OBJECT
REQUEST
RESPONSE
Obj
Var
Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
8
16-Bit Delta Counter
Without Flag
129, 130
00, 01
16
Server will return Unknown
Object to this request
21
0
Frozen Counter - All
Variations
1
06
32
Server will return variation 9
data
1
32-Bit Frozen
Counter
129, 130
00, 01
40
Server will return Unknown
Object to this request
2
16-Bit Frozen
Counter
129, 130
00, 01
24
Server will return Unknown
Object to this request
3
32-Bit Frozen Delta
Counter
40
Server will return Unknown
Object to this request
4
16-Bit Frozen Delta
Counter
24
Server will return Unknown
Object to this request
5
32-Bit Frozen
Counter With Time Of
Freeze
88
Server will return Unknown
Object to this request
6
16-Bit Frozen
Counter With Time Of
Freeze
72
Server will return Unknown
Object to this request
7
32-Bit Frozen Delta
Counter With Time Of
Freeze
88
Server will return Unknown
Object to this request
8
16-Bit Frozen Delta
Counter With Time Of
Freeze
72
Server will return Unknown
Object to this request
9
32-Bit Frozen
Counter Without Flag
1
06
129, 130
00, 01
32
Server will return this
variation
10
16-Bit Frozen
Counter Without Flag
1
06
129, 130
00, 01
16
Server will return this
variation (counter upper 16-
bits removed)
11
32-Bit Frozen Delta
Counter Without Flag
32
Server will return Unknown
Object to this request
12
16-Bit Frozen Delta
Counter Without Flag
16
Server will return Unknown
Object to this request
22
0
Counter Change
Event - All Variations
1
06, 07,
08
Server will parse this request
and return no data
1
32-Bit Counter
Change Event
Without Time
129, 130
17, 28
40
Server will return Unknown
Object to this request
2
16-Bit Counter
Change Event
Without Time
129, 130
17, 28
24
Server will return Unknown
Object to this request
3
32-Bit Delta Counter
Change Event
Without Time
40
Server will return Unknown
Object to this request
Vista de página 123