3.7 Communication Error Codes
3.7.1 General Command Errors
The IED slave address referenced in the
command is not defined in the module. Check
to make sure there is an entry in the slave
table for each slave device referenced in the
command list.
This command is not valid. Check to make
sure the slave address parameter is greater
than or equal to zero and that the point count
is not set to zero.
The data object in the command is not
supported by the module. Refer to the DNP
subset for the Master Port.
Command function not supported
The function specified in the command is not
supported for the object type selected. Refer to
the DNP subset for the Master Port.
Command variation not supported
The variation specified in the command is not
supported for the object type selected.
The command is not supported unless Binary
Output Status is enabled
The command is not supported unless Analog
Output Status is enabled
Invalid time/date poll command
This time/date object poll command is not
valid.
Time/date poll command cannot
execute
This time/date object poll command cannot
execute because the module's clock has not
been synced from a valid source (from PLC or
connected Client)