Contents MVI56E-DNPNET ♦ ControlLogix Platform
User Manual DNPNET Ethernet Client/Server Communication Module
Page 104 of 140 ProSoft Technology, Inc.
February 13, 2015
The module responds to the request with a read block 9970 with the following format.
This is the next block requested by the module.
This field contains the four-digit year for the new time value.
This field contains the month value for the new time. Valid
entry for this field is in the range of 1 to 12.
This field contains the day value for the new time. Valid entry
for this field is in the range of 1 to 31.
This field contains the hour value for the new time. Valid entry
for this field is in the range of 0 to 23.
This field contains the minute value for the new time. Valid
entry for this field is in the range of 0 to 59.
This field contains the second value for the new time. Valid
entry for this field is in the range of 0 to 59.
This field contains the millisecond value for the new time. Valid
entry for this field is in the range of 0 to 999.
Remote Time
Synchronization
This field informs the PLC if the date and time passed has
been synchronized with a remote DNP3 Ethernet Client device
on the module's server port.
1 = time has been set on the DNP3 Ethernet network.
0 = waiting for time sync from DNP3 Ethernet Client.
This field contains the block identification code of 9970 for the
block.
Block 9971: Set Module Time From CLX Processor
Block identification code 9971 passes the clock time in the ControlLogix processsor to the
module. The date and time provided will be used to set the module's DNPNET clock.
This field contains the block identification code of 9971 for the
block.
This field contains the four-digit year for the new time value.
This field contains the month value for the new time. Valid
entry for this field is in the range of 1 to 12.
This field contains the day value for the new time. Valid entry
for this field is in the range of 1 to 31.