DNPNET.CONFIG.DNP3
_Server.A32I_Class
This parameter specifies the default class to
be utilized for all the 32-bit analog input points
in the DNP database that are not defined in
the override list section.
DNPNET.CONFIG.DNP3
_Server.Float_Class
This parameter specifies the default class to
be utilized for all the float input points in the
DNP database that are not defined in the
override list section.
DNPNET.CONFIG.DNP3
_Server.Double_Class
This parameter specifies the default class to
be utilized for all the double input points in the
DNP database that are not defined in the
override list section.
DNPNET.CONFIG.DNP3
_Server.AI_Deadband
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the 16-bit analog input point
type in the DNP database.
DNPNET.CONFIG.DNP3
_Server.A32I_Deadband
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the 32-bit analog input point
type in the DNP database.
DNPNET.CONFIG.DNP3
_Server.Float_Deadband
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the float input point type in the
DNP database.
DNPNET.CONFIG.DNP3
_Server.Double_Deadba
nd
0 to maximum
double value
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the double input point type in
the DNP database.
DNPNET.CONFIG.DNP3
_Server.SelectOperate_
Arm_Time
Time period after select command received in
which operate command will be performed.
After the select command is received, the
operate command will only be honored if it
arrives within this period of time.
DNPNET.CONFIG.DNP3
_Server.Write_Time_
Interval
Time interval to set the need time IIN bit
(0=never), which will cause the client to write
the time. Stored in milliseconds in the module
memory.
DNPNET.CONFIG.DNP3
_Server.Spare1_always_
0
Coded Value
0=Never
1=Sometimes
2=Always
IED can request acknowledgement from client
station when sending data.
DNPNET.CONFIG.DNP3
_Server.Spare2_always_
0
Time period to wait for client Data Link
confirmation of last frame sent. This time is in
milliseconds. This parameter is only used if the
frame is sent with confirmation requested.
DNPNET.CONFIG.DNP3
_Server.Spare3_always_
0
Maximum number of retries at the Data Link
level to obtain a confirmation. If this value is
set to 0, retries are disabled at the data link
level of the protocol. This parameter is only
used if the frame is sent with confirmation
requested.