Tag Name
Range
Description
Class
1 to 3
Class number assigned to point number
specified
Deadband
0 to 32767
Deadband assigned to point number specified
DNPNET.CONFIG.DNP_Serv
er_Override.Analog32_Inputs.
n/a
Number of 32-bit analog input points contained
in the IED database to be transferred to the
PLC and obtained from the attached IED units.
This array size ranges from 0 to 500.
Point_Number
0 to Number of
points configured
Point number index to be overridden
Class
1 to 3
Class number assigned to point number
specified
Deadband
0 to 32767
Deadband assigned to point number specified
DNPNET.CONFIG.DNP_Serv
er_Override.Float_Inputs.
n/a
Number of float input points contained in the
IED database to be transferred to the PLC and
obtained from the attached IED units
This array size ranges from 0 to 500.
Point_Number
0 to Number of
points configured
Point number index to be overridden
Class
1 to 3
Class number assigned to point number
specified
Deadband
0 to 32767
Deadband assigned to point number specified
DNPNET.CONFIG.DNP_Serv
er_Override.Double_Inputs.
n/a
Number of counter points contained in the IED
database to be transferred to the PLC and
obtained from the attached IED units. This
array size ranges from 0 to 250.
Point_Number
0 to Number of
points configured
Point number index to be overridden
Class
1 to 3
Class number assigned to point number
specified
Deadband
0 to 32767
Deadband assigned to point number specified