Configuring the MVI56E-SIE Module MVI56E-SIE ♦ ControlLogix Platform
User Manual Client Communication Module
Page 72 of 168 ProSoft Technology, Inc.
September 6, 2012
5 Select each parameter and edit its value according to the table below. (Use
the IP address applicable to your network.)
Enables the command to be executed.
In this example, the data will be sourced from register 1000 in
the module’s internal database, which is by default the first
register in the module’s Write Data area. See note below.
A poll interval of 0 enables the fastest polling possible.
In this example, five consecutive registers will be written, starting
at Data Block 1, Address 0 (DB1.DBW0).
The INT data type will be used, so there is no need to consider
word or byte order.
In this example, the S7-300 Siemens processor addressed in
this command is at 10.1.3.179.
This is the correct value for the S7-300 processor.
In this example, the rack number is 0.
In this example, slot 2 is being used.
This parameter is ignored in a command to an S7-300
processor, so it is left at its default value here.
In this example, data is being moved into the Siemens
processor.
In this example, the INT data type is used.
In this example, the DB address type is used.
In this example, DB Number 1 is used.
In this example, the data’s destination address is 0.
Note: In this example, the Internal Address parameter configures this command to source the
Write data from the first register in the module’s Write Data area. The start address of the module’s
Write Data area is determined by the Write Register Start parameter in the module configuration.
By default, the Write Register Start parameter is set to 1000.