MVI56E-SIE ControlLogix Platform Diagnostics and Troubleshooting
Client Communication Module User Manual
ProSoft Technology, Inc. Page 123 of 168
September 6, 2012
4.2.4 Monitoring Backplane Information
Use the BACKPLANE menu to view the backplane status information for the
MVI56E-SIE module.
Backplane Status
Use the Status menu to view current backplane status, including
Number of retries
Backplane status
Fail count
Number of words read
Number of words written
Number of words parsed
Error count
Command count
During normal operation, the read, write, and parsing values should increment
continuously, while the error value should not increment.
The status values on this menu correspond with members of the Status Data
Definition (page 127).