MVI56E-SIE ♦ ControlLogix Platform Configuring the MVI56E-SIE Module
Client Communication Module User Manual
ProSoft Technology, Inc. Page 57 of 168
September 6, 2012
Internal Address
0 to 65535 (for bit-level addressing) or
0 to 4999 (for word-level addressing)
This parameter specifies the database address in the module's internal database
to use as the destination for data brought in by a read command or as the source
for data to be sent out by a write command. The database address is interpreted
as a bit address or a 16-bit word (register) address, depending on the Siemens
Industrial Ethernet’s Data Type used in the command. If Data Type – Bool is
used in the command list, then the database address will be interpreted as a bit
address. When any other data types are used, then the database address is
interpreted as 16-bit word (register) address.
Poll Interval
0 to 65535
This parameter specifies the minimum interval between issuances of a command
during continuous command execution (Enable code of 1). The parameter is
entered in tenths of a second. Therefore, if a value of 100 is entered for a
command, the command executes no more frequently than every 10 seconds.
Reg Count
Regs: This Count will depend on the Siemens processor type
Coils: This Count will depend on the Siemens processor type
Below are the tables of the max reg count limit for three of the Siemens
processors:
CPU315-2 DP
Data Block: