Configuring the MVI56E-SIE Module MVI56E-SIE ControlLogix Platform
User Manual Client Communication Module
Page 62 of 168 ProSoft Technology, Inc.
September 6, 2012
CPU224XP:
Data Block:
Address Type
Function
Data Type
Max Read
Max Write
DB
READ
BOOL
1
Write
BOOL
1
READ
BYTE
222
Write
BYTE
212
READ
DINT
55
Write
DINT
53
READ
REAL
55
Write
REAL
53
READ
INT
111
Write
INT
106
Flag:
Address Type
Function
Data Type
Max Reg Cnt
Max Reg Cnt
Flag
READ
BOOL
1
Write
BOOL
1
READ
BYTE
32
Write
BYTE
32
READ
DINT
8
Write
DINT
8
READ
REAL
8
Write
REAL
8
READ
INT
16
Write
INT
16