Reference MVI56E-SIE ♦ ControlLogix Platform
User Manual Client Communication Module
Page 146 of 168 ProSoft Technology, Inc.
September 6, 2012
Block Response from Module to Processor
Number of commands added to command queue
Controller Tags
The SIE.CONTROL controller tag array holds all the values needed to create one
Command Control block, have it sent to the module, and control the processing
of the returned response block.
Enter a decimal value representing the quantity of commands to be
requested in the Command Control block (1 to 16). This value is
used by the ladder logic to generate the Command Control Block ID.
The rightmost digits of the Command Control Block ID are the
number of commands requested by the block.
Enter the Client to issue the commands to (0 to 19)
Enter the ROW NUMBER of the command in the SIE Client x
Command List in Prosoft Configuration Builder minus 1. This is a
16-element array. Each element holds one Command Index.
Enter a 1 (enable) or a 0 (disable) to select which commands on the
configuration's Client x Command List will be executed during
routine polling. There is one 16-bit word for each of the 30 Clients.
Each of the 16 bits corresponds to one of the 16 commands
available to each Client. The state of these WriteCmdBits overrides
whatever value may be assigned to the Enable parameter in the
configuration.
Note: This parameter only affects routine polling. It has no effect on
Command Control blocks.
Set this tag to 1 to trigger the execution of a Command Control
block after all the other parameters have been entered.