Prosoft-technology MVI56E-LDM Manual do Utilizador Página 80

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 264
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 79
CIP API Functions ControlLogix Platform "C" Programmable
Developer's Manual Linux Application Development Module
Page 74 of 264 ProSoft Technology, Inc.
March 12, 2014
OCXcip_OpenNB
Syntax
int OCXcip_OpenNB(OXCHANDLE *apihandle);
Parameters
apiHandle
pointer to variable of type OCXHANDLE
Description
OCXcip_OpenNB acquires access to the CIP API and sets apiHandle to a unique ID
that the application uses in subsequent functions. This function must be called
before any of the other CIP API functions can be used.
Most applications will use OCXcpi_Open instead of this function. This version of
the open function allows access to a limited subset of API functions that are not
related to the ControlLogix backplane. This can be useful in some situations if an
application separate from the host application needs access to a device such as
the alphanumeric display.
An application should only use either OCXcip_Open or OCXcip_OpenNB, but never
both.
The API functions that can be accessed after calling OCXcip_OpenNB are:
OCXcip_Close
OCXcip_GetDisplay
OCXcip_GetUserLED
OCXcip_GetLED3
OCXcip_GetIdObject
OCXcip_GetModuleStatus
OCXcip_GetSwitchPosition
OCXcip_GetVersionInfo
OCXcip_ReadSRAM
OCXcip_SetDisplay
OCXcip_SetUserLED
OCXcip_SetLED3
OCXcip_SetModuleStatus
OCXcip_Sleep
IMPORTANT: Once the API has been opened, OCXcip_Close should always be
called before exiting the application.
Return Value
OCX_SUCCESS
API was opened successfully
OCX_ERR_REOPEN
API is already open
Note: OCX_ERR_NODEVICE will be returned if the backplane device driver is not
loaded.
Vista de página 79