104S v2 ♦ ProLinx Gateway IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v2.xx) Protocol Manual
Page 82 of 157 ProSoft Technology, Inc.
Data Type Level
The user may configure if a data type should generate events or not. Each data
type has a configuration parameter to control the generation of events:
In the example above, only the M_SP_NA points would generate events.
Point Level
You can configure whether or not each point should generate events on a point-
by-point basis by using the Group field for each point configuration. Set the value
as 40000000 to disable the generation of events for any specific point.
March 19, 2010