104S v2 ProLinx Gateway IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v2.xx) Protocol Manual
Page 62 of 157 ProSoft Technology, Inc.
March 19, 2010
3.4 Using Control (Command) Points
The following control points are supported by the 104S v2 gateway:
Symbol Description
C_SC_NA Single-Point Command
C_DC_NA Dual-Point Command
C_RC_NA Step-Point Command
C_SE_NA Measured Normalized Point Command
C_SE_NB Measured Scaled-Point Command
C_SE_NC Measured Short Floating-Point Command
Each control point is identified by its Information Object Address. For each
control point, configure the following parameters:
Point #: This is the information object address of the point. It identifies the point
in the network. This address must be unique for each Common ASDU Address in
the network.
DB Address: This is the database location in the 104S v2 gateway associated
with the point.
Monitor Point #-Monitor DB Address- The user might (optionally) configure a
monitor point to be sent by the 104S v2 module gatewayt receives the command
for that specific point.