Reference 104S v2 ♦ ProLinx Gateway
Protocol Manual (Firmware v2.xx)
ProSoft Technology, Inc. Page 129 of 157
March 19, 2010
5.7.3 Selection of standard ASDUs
Process information in monitor direction
(Station-specific parameter, mark each Type ID 'X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
⌧ <1> := Single-point information M_SP_NA_1
⌧ <3> := Double-point information M_DP_NA_1
⌧ <5> := Step position information M_ST_NA_1
<7> := Bitstring of 32 bit M_BO_NA_1
⌧ <9> := Measured value, normalized value M_ME_NA_1
⌧ <11> := Measured value, scaled value M_ME_NB_1
⌧ <13> := Measured value, short floating point value M_ME_NC_I
⌧ <15> := Integrated totals M_IT_NA_1
<20> := Packed single-point information
with status change detection M_PS_NA_1
<21> := Measured value, normalized value
without quality descriptor M_ME_ND_1
⌧ <30> := Single-point information
with time tag CP56Time2a M_SP_TB_1
⌧ <31> := Double-point information
with time tag CP56Time2A M_DP_TB_1
⌧ <32> := Step position information
with time tag CP56Time2A M_ST_TB_1
<33> := Bitstring of 32 bit with time tag CP56Time2A M_BO_TB_1
⌧ <34> := Measured value, normalized value
with time tag CP56Time2A M_ME_TD_1
⌧ <35> := Measured value, scaled value
with time tag CP56Time2A M_ME_TE_1
⌧ <36> := Measured value, short floating point value
with time tag CP56Time2A M _ME_TF_1
⌧ <37> := Integrated totals with time tag CP56Time2A M_IT_TB_1
<38> := Event of protection equipment
with time tag CP56Time2A M_EP_TD_1
<39> := Packed start events of protection equipment
with time tag CP56time2A M_EP_TE_1
<40> := Packed output circuit information of
protection equipment with
time tag CP56Time2a M_EP_TF_1