Reference 5204SE-MNET-PDPMV1 ♦ ProLinx Gateway
User Manual Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc. Page 221 of 235
December 22, 2009
4.7.5 Command Error Codes
Errors reported from the command list of the gateway require 8-bytes or 4-words
per command. If the first 7 bytes of the error are 0xFF, this is a gateway
generated error as follows:
Value of Last Byte Error Definition
0x00 Too few parameters for command in command list section of configuration
file.
0x01 Invalid type value specified for command.
0x02 Invalid database offset specified for command.
0x03 Invalid swap type code specified for command.
0x04 Invalid database trigger address
0x05 Invalid database address and count combination
0x10 Invalid function code specified for command.
0xFF Response timeout for command recognized.
Refer to Error Codes (page 219) for an explanation of other error codes.
The 8-bytes (4-words) represent the extended words 5 to 8 in response
messages.