5204SE-MNET-PDPMV1 ProLinx Gateway Reference
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master User Manual
Page 182 of 235 ProSoft Technology, Inc.
December 22, 2009
Variable Name Size/Type Description
In - Fault 1
16-bit Integer
If "Invalid other" is returned in the Acyclic Message
Status Word in the header of the response, information
about the fault can be found here. Refer to Acyclic
Message Status Word (page 218)
0001h: Address out of range.
000Ah: Failed to execute request. Refer to Return Codes
(page 219) for additional information.
000Bh: Remote station failure. Refer to Return Codes
(page 219) for additional information.
00FFh: gateway not initialized.
In - SetAddressData 200-element
8-bit Byte
Array
Additional message data that may be returned by the
slave
In - SetSlaveAddActive 1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP
message has been initiated and is being processed.
In - SetSlaveAddError 1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP
response is not successfully received. When this bit is
set, it indicates your control and sequencing logic should
retry the command.
In -
SetSlaveAddSuccess
1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP
response is successfully received and the PROFIBUS
cyclic input data variables have been updated.