Reference 5204SE-MNET-PDPMV1 ProLinx Gateway
User Manual Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master
ProSoft Technology, Inc. Page 197 of 235
December 22, 2009
02h: Master Station ready to enter Token ring (there is not yet any Token
transmission)
03h: Master Station in Token Ring (Token transmission through the station)
04h: Station does not exist
Fault Information
If "Invalid Other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here. Refer to Acyclic
Message Status Word (page 218).
000Ah: Failed to build Live List.
00FFh: gateway offline (not initialized or no valid database)