Prosoft-technology 5204SE-MNET-PDPMV1 Manual do Utilizador Página 122

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 235
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 121
5204SE-MNET-PDPMV1 ProLinx Gateway Reference
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master User Manual
Page 122 of 235 ProSoft Technology, Inc.
December 22, 2009
Variable Name
Size/Type Description
In - Length 1
8-bit Byte
Number of diagnostic bytes returned by the slave and
help in the In-Response Data[ ] variable array
In - MessageDone 1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP
response is successfully received.
In - MessageError 1
Single-bit
Boolean
The DFB will set this bit when the Modbus TCP/IP
response is not successfully received. When this bit is
set, it indicates your control and sequencing logic should
retry the command.
DFB Acyclic Mailbox Message: Get Slave Configuration - M340
This acyclic message reads the actual configuration (identifier bytes) of a
specified slave.
Note: The response data size depends on the actual slave implementation. Range 6 to 244.
MNETDPV1_MAILVAR_GetConfig Variables - M340
This variable structure is the one to use with your control and sequencing logic
when you want to retrieve configuration information from a specific PROFIBUS
network slave.
Vista de página 121
1 2 ... 117 118 119 120 121 122 123 124 125 126 127 ... 234 235

Comentários a estes Manuais

Sem comentários