Reference ProLinx-HART ♦ ProLinx Gateway
Driver Manual HART Master with Analog I/O
Page 84 of 104 ProSoft Technology, Inc.
October 13, 2011
COMMAND 110 - Read All Dynamic Variables
Description
This command gets all dynamic Variables.
Write Parameters
NONE
Floating Point Data Returned
Word High Byte Low Byte
0 Primary Variable
1
2 Second Variable
3
4 Third Variable
5
6 Fourth Variable
7
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Primary Variable Units Code Second Variable Units Code
2 Third Variable Units Code Fourth Variable Units Code
Vista de página 83