HART Protocol Configuration ProLinx-HART ♦ ProLinx Gateway
Driver Manual HART Master with Analog I/O
Page 36 of 104 ProSoft Technology, Inc.
October 13, 2011
3.3.19 Fixed Data
Up to 250 HEX values separated by space
This parameter is a string of HEX values to be sent with the HART command. There
should be at least the number of bytes specified in the "Byte Count" parameter. The
bytes should be written in hexadecimal format and separated by a space. This data will
be sent if the Parameter "Write DB Address" is "-1" and "Byte Count" is greater than "0",
and it will be sent in the same order that they are written.