ProLinx-HART ♦ ProLinx Gateway Reference
HART Master with Analog I/O Driver Manual
ProSoft Technology, Inc. Page 45 of 104
October 13, 2011
COMMAND 03 - Read Dynamic Variables
Description
This command gets the current and four (predefined) dynamic Variables.
Write Parameters
NONE
Floating Point Data Returned
Word High Byte Low Byte
0 Current (mA)
1
2 Primary Variable
3
4 Second Variable
5
6 Third Variable
7
8 Fourth Variable
9
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Primary Variable Units Code Second Variable Units Code
2 Third Variable Units Code Fourth Variable Units Code
Vista de página 44