Verify the Chassis Size
You must configure the chassis size for the ILX34-AENWG before you can make
any I/O connections (page
31). The default setting for the chassis size is 1 slot,
which represents the adapter by itself.
When the adapter's non-volatile chassis size does not match the actual number
of modules present on its backplane, the adapter does not make any I/O
connections and an error occurs, as shown in the M
ODULE PROPERTIES dialog
box.
This procedure synchronizes the chassis size value from the RSLogix 5000
software into the ILX34-AENWG hardware. You must be online to perform this
procedure.
1 Verify that RSLogix 5000 software is online to the processor.
2 Double-click the ILX34-AENWG
adapter under I/O CONFIGURATION in the
C
ONTROLLER ORGANIZATION window. This action opens the MODULE
PROPERTIES dialog box.
3 On the M
ODULE PROPERTIES dialog box, click the CONNECTION tab. Notice
that the M
ODULE FAULT area of the dialog box contains information about the
error code.