MVI69L-MBS ♦ CompactLogix Platform Reference
Communication Module User Manual
ProSoft Technology, Inc. Page 133 of 154
January 6, 2014
Command Control Block Count: Total number of Command Control blocks received
from the processor.
Error Block Count: Total number of block errors recognized by the module.
Port 1 Current Error: For a slave port, this field contains the value of the current
error code returned. For a master port, this field contains the index of the currently
executing command.
Port 1 Last Error: For a slave port, this field contains the value of the last error code
returned. For a master port, this field contains the index of the command with an
error.
7.4.11 Set Port and Command Active Bits Block
Block 9500: Set Port and command active bits
This block enables and disables port 1, as well as individual Master commands
for a port.
Block 9500: Request from Processor to Module
Write Block ID: 9500 to set port and command enable/disable state
Port 1 active state: 0=disabled, 1=enabled
Command enable bits for Port 1 commands (0=disabled, 1=enabled)
Command enable bits for Port 2 commands (0=disabled, 1=enabled)
Block 9500: Response from Module to Processor
Read Block ID: 9500 requested by processor.
Write Block ID: To be used by the processor in its next Write block.
Comentários a estes Manuais