MVI69L-MBS CompactLogix Platform Reference
Communication Module User Manual
ProSoft Technology, Inc. Page 129 of 154
January 6, 2014
7.4.7 Get Event with Data Status Block
Block 8100: Get Event with Data Status
This block requests status data for Event with Data Commands.
Block 8100: Request from Processor to Module
Offset
Description
0
Write Block ID: 8100 status data request for Event with Data Commands.
1 to 239
Spare
Block 8100: Response from Module to Processor
Offset
Description
0
Read Block ID: 8100 status data for Event with Data Commands.
1
Write Block ID: To be used by the processor in its next Write block.
2
Event command status for Port 1:
0=No message active
1=Waiting to execute command
2=Command complete
3
Error code for last command executed for Port 1
4 to 239
Spare