MVI69-HART ♦ CompactLogix Platform Reference
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 155 of 169
March 29, 2012
COMMAND 108 - Write Burst Mode Command Number
Description
This command sets the command number that the HART device will use in Burst
Mode.
Write Parameters
Word High Byte Low Byte
0 Burst Mode Command Number Burst Mode Command Number
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Burst Mode Command Number 0