
MVI69-HART ♦ CompactLogix Platform Reference
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 145 of 169
March 29, 2012
COMMAND 50 - Read Dynamic Variable Assignments
Description
This command gets the actual assignment of the Dynamic Variables returned
with command 3.
Write Parameters
NONE
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Transmitter Variable Code For Primary
Variable
Transmitter Variable Code For Second
Variable
2 Transmitter Variable Code For Third
Variable
Transmitter Variable Code For Fourth
Variable
Comentários a estes Manuais