Prosoft-technology MVI56-101S Manual do Utilizador Página 61

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 60
MVI56-101S ControlLogix Platform Configuring the MVI56-101S Module
IEC 60870-5-101 Slave Communication Module User Manual
ProSoft Technology, Inc. Page 61 of 193
August 2, 2011
2.12 [M_IT_NA_1]
This section defines the monitored integrated totals (counter) database. This
information is sourced from the database and is transferred to the remote Master
unit. This section takes the following parameters:
P
OINT #
DB
ADDRESS
G
ROUPS
IV
DB BIT
Each point consumes four 8-bit bytes (two 16-bit words). The DB ADDRESS value
corresponds to the double-word offset address in the database.
The DB
ADDRESS should be located in a database area that is being constantly
moved from the module to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.
Vista de página 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 192 193

Comentários a estes Manuais

Sem comentários