IEC 60870-5-101 Slave Interoperability Statement MVI56-101S ♦ ControlLogix Platform
User Manual IEC 60870-5-101 Slave Communication Module
Page 172 of 193 ProSoft Technology, Inc.
August 2, 2011
6.6 Selection of Standard ASDUs
6.6.1 Process Information in Monitor Direction
(Station-specific parameter; mark each Type ID "X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
<1> := Single-point information M_SP_NA_1
<2> := Single-point information with time tag M_SP_TA_1
<3> := Double-point information M_DP_NA_1
<4> := Double-point information with time tag M_DP_TA_1
<5> := Step position information M_ST_NA_1
<6> := Step position information with time tag M_ST_TA_1
<7> := Bitstring of 32 bit M_BO_NA_1
<8> := Bitstring of 32 bit with time tag M_BO_TA_1
<9> := Measured value, normalized value M_ME_NA_1
<10> := Measured value, normalized value with time tag M_ME_TA_1
<11> := Measured value, scaled value M_ME_NB_1
<12> := Measured value, scaled value with time tag M_ME_TB_1
<13> := Measured value, short floating-point value M_ME_NC_I
<14> := Measured value, short floating-point value with time tag
M_ME_TC_1
<15> := Integrated totals M_IT_NA_1
<16> := Integrated totals with time tag M_IT_TA_1
<17> := Event of protection equipment with time tag M_EP_TA_1
<18> := Packed start events of protection equipment with time tag
M_EP_TB_1
<19> := Packed output circuit information of protection equipment with
time tag M_EP_TC_1
<20> := Packed single-point information with status change detection
M_PS_NA_1
<21> := Measured value, normalized value without quality description
M_ME_ND_1
<30> := Single-point information with time tag CP56Time2a
M_SP_TB_1
<31> := Double-point information with time tag CP56Time2a
M_DP_TB_1
<32> := Step position information with time tag CP56Time2a
M_ST_TB_1
<33> := Bitstring of 32 bit with time tag CP56Time2a M_BO_TB_1
<34> := Measured value, normalized value with time tag CP56Time2a
M_ME_TD_1