Prosoft-technology MVI69-ADM Manual do Utilizador Página 21

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 342
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 20
MVI-ADM 'C' Programmable Preparing the MVI-ADM Module
'C' Programmable Application Development Module Developer's Guide
ProSoft Technology, Inc. Page 21 of 342
February 20, 2013
RS-232: Null Modem Connection (No Hardware Handshaking)
This type of connection can be used to connect the module to a computer or field
device communication port.
Note: For most null modem connections where hardware handshaking is not required, the Use
CTS Line parameter should be set to N and no jumper will be required between Pins 7 (RTS) and 8
(CTS) on the connector. If the port is configured with the Use CTS Line set to Y, then a jumper is
required between the RTS and the CTS lines on the port connection.
Vista de página 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 341 342

Comentários a estes Manuais

Sem comentários