Reference MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual PROFIBUS DPV1 Master
Page 240 of 255 ProSoft Technology, Inc.
March 22, 2011
Byte Offset
Start End Name Description
14 15 PROFIBUS Output Data size The number of words to transfer from the processor in the
PROFIBUS output space during the output data transfer. Value
is selected during user configuration
16 17 Reserved Reserved for future use
18 19 Reserved Reserved for future use
20 21 Reserved Reserved for future use
22 22 Input Data Byte Swap User-configured flag to indicate if input data is swapped before
being placed in the input image for the controller.
0=No swapping
Not 0=Swap bytes
23 23 Output Data Byte Swap User-configured flag to indicate if output data is swapped after
being received from the output image of the controller.
0=No swapping
Not 0=Swap bytes
24 24 Module software major version
number.
MVI56 module application software version number
Bits
16 8 7 0
High Byte Low Byte
25 25 Module software minor version
number
26 41 PROFIBUS Slave Configured List This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. The associate bit is set if the slave
is present in the database. For the bit/slave relationship, refer to
the Slave List Structure below.
42 57 PROFIBUS Data Transfer Status This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. The associated bit is set if the slave
has reached or retained the "Data Exchange" state at least once
during the last three data cycles. For the bit/slave relationship,
refer to the Slave List Structure below.
58 73 PROFIBUS Slave Diagnostic
Status
This is a 16-byte array with bit fields where one bit is assigned to
each slave station address. When a slave leaves the "Deactive"
state for the first time, the associated bit is set. This bit is then
cleared when the slave enters "Data Exchange" state. If a slave
indicates "Extended Diagnostics" when it is in "Data Exchange"
state, the associated bit is set. For the bit/slave relationship,
refer to the Slave List Structure below.
Slave List Structure