Prosoft-technology ILX69-PBS Manual do Utilizador Página 67

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 66
ILX69-PBS CompactLogix or MicroLogix Platform Contents
PROFIBUS Slave Communication Module User Manual
ProSoft Technology, Inc. Page 67 of 102
March 20, 2015
DPV1 Error Codes
Below are the PROFIBUS DPV1 error codes.
Error Code 1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Error Code (see below)
Error Class (see below)
Error Class
Description
Error Code
0 to 9
Reserved
10
Application
0 = Read Error
1 = Write Error
2 = Module Failure
3 to 7 = Reserved
8 = Version Conflict
9 = Feature not Supported
10 to 15 = User Specific
11
Access
0 = Invalid Index
1 = Write Length Error
2 = Invalid Slot
3 = Type Conflict
4 = Invalid Area
5 = State Conflict
6 = Access Denied
7 = Invalid Range
8 = Invalid Parameter
9 = Invalid Type
10 to 15 = User Specific
12
Resource
0 = Read Constrain Conflict
1 = Write Constrain Conflict
2 = Resource Busy
3 = Resource Unavailable
4 to 7 = Reserved
8 to 15 = User Specific
13 to15
User Specific
Error Code 2
An error code 2 is application specific.
Vista de página 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72 ... 101 102

Comentários a estes Manuais

Sem comentários