MNET ♦ ProLinx Gateway Diagnostics and Troubleshooting
Modbus TCP/IP Interface Module Driver Manual
ProSoft Technology, Inc. Page 51 of 78
September 1, 2010
6 0064 Invalid Float Start value (<0)
7 0128 Invalid Float Offset value
8 0256 Reserved
9 0512 Reserved
10 1024 Reserved
11 2048 Reserved
12 4096 Reserved
13 8192 Reserved
14 16383 Reserved
15 -32768 Reserved (Signed Integer value shown)
Registers 6008 and 6009 contain information about the most recent
communication errors. The Current Error (6008) will have a non-zero value if the
currently executing Client command experiences an error. The Last Error (6009)
will store the most recent non-zero value error code that was reported by the
Client the last time it experienced an error. Note that this value is retentive. This
register will hold the last error value until the memory is cleared by a restart,
reset, cold-boot, or warm-boot operation. Therefore, any value you see here
may indicate an error that could have occurred at any time since the module was
last restarted and may not indicate a current or recent error. For details on error
codes, see MNET Client Command List Error Data.
3.3.2 MNET Server Port 2000 Status Error Locations
The following table lists the status error locations for MNET Server Port 2000
errors.
Internal Database Address Description
6200 Number of Command Requests
6201 Number of Command Responses
6202 Number of Command Errors
6203 Number of Requests
6204 Number of Responses
6205 Number of Errors Sent
6206 Number of Errors Received
6207 Configuration Error Word
6208 Current Error Code
6209 Last Error Code
Refer to the Error Codes section in this manual to interpret the status/error codes
present in the data area.