HART ProLinx Gateway Reference
HART Master Driver Manual
Page 88 of 119 ProSoft Technology, Inc.
July 7, 2009
COMMAND 57 - Read Unit Tag Descriptor Date
Description
This command reads an ASCII Tag which identifies the device, an ASCII
descriptor of the device and the last Date it has been configured.
Write Parameters
NONE
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 TAG ASCII Character 0 TAG ASCII Character 1
2 TAG ASCII Character 2 TAG ASCII Character 3
3 TAG ASCII Character 4 TAG ASCII Character 5
4 TAG ASCII Character 6 TAG ASCII Character 7
5 Descriptor ASCII Character 0 Message ASCII Character 1
.
.
.
.
.
.
12 Descriptor ASCII Character 14 Message ASCII Character 15
13 Date Date
14 Date 0
Vista de página 87