PLX8x-MNET-61850 Communication Gateway Example Configurations
Modbus TCP/IP to IEC 61850 User Manual
ProSoft Technology, Inc. Page 87 of 228
May 14, 2014
3.8 Updating a CID File
Changes may need to be made to the CID, ICD, or SCD files after the ProSoft
gateway configuration has been setup.
Perhaps on your IED you have modified a DATA-SET that’s used by the ProSoft
gateway, or added or removed some Data Attributes. When you make changes
like this, its easy to update ProSoft 61850 Configuration Manager with this
information.
Click on the CID, SCD, OR ICD filename in the Device View section of ProSoft
61850 Configuration Manager. Choose UPDATE IED.
It will prompt you to browse for the new file. Oftentimes you’ll use the exact same
filename as you used when you imported the file into ProSoft 61850
Configuration Manager the first time.