Prosoft-technology PLX8X-MNET-61850 Manual do Utilizador Página 33

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 228
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 32
PLX8x-MNET-61850 Communication Gateway ProSoft 61850 Configuration Manager
Modbus TCP/IP to IEC 61850 User Manual
ProSoft Technology, Inc. Page 33 of 228
May 14, 2014
CONNECTION TIMEOUT: 0 to 1200 seconds. This is the number of seconds the
Server will wait to receive new data. If the Modbus TCP/IP Server does not
receive any new data during this time, it will close the Ethernet socket
connection. The default value is 60.
The gateway supports multiple MNET servers and MBAP servers.
ENCAPSULATED MODBUS: This is the number of Modbus TCP/IP Client devices
that will communicate with the gateway using TCP/IP Service Port 2000. These
are devices that use Modbus RTU serial-style message structures enclosed in an
Ethernet wrapper.
MBAP : This is the number of Modbus TCP/IP Client devices that will
communicate with the gateway using Schneider Electric MBAP-style messages
on TCP/IP Service Port 502.
2.2.1 Modbus TCP/IP Client and Server - Lookup
Vista de página 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 227 228

Comentários a estes Manuais

Sem comentários