Prosoft-technology PLX8X-MNET-61850 Manual do Utilizador Página 166

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 228
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 165
Reference PLX8x-MNET-61850 Communication Gateway
User Manual Modbus TCP/IP to IEC 61850
Page 166 of 228 ProSoft Technology, Inc.
May 14, 2014
6.4.7 Modbus TCP/IP Server
Modbus TCP/IP Server Startup Sequence:
a Connect to Event Logger
b Connect to tag database Error message in event log on fail
c Parse configuration file Error message if cannot create configuration
object
d Connect to system tag database
e Initialize diagnostics
f Connect to MCP Error message in event log on fail
g Create server pool
h Server pool creates a server thread for each configured server
i Inform MCP that driver is ready to run
j Wait for run signal from MCP
k Run server communications: wait for Client to connect
l If receives quit signal from MCP clean up threads and exit process
Each Client will try to connect in a loop until the connection is made. If the
attempt to connect fails, it will wait 100ms and try again. If a connection is lost it
start trying to connect the same as during startup.
The server will disconnect on connection loss or when there is no communication
for a timeout period. It will then begin listening for a connection request from a
Client.
Vista de página 165
1 2 ... 161 162 163 164 165 166 167 168 169 170 171 ... 227 228

Comentários a estes Manuais

Sem comentários