Diagnostics and Troubleshooting PLX8x-MNET-61850 Communication Gateway
User Manual Modbus TCP/IP to IEC 61850
Page 118 of 228 ProSoft Technology, Inc.
May 14, 2014
Modbus TCP/IP Server
The following Modbus TCP/IP server diagnostic data is available from the
gateway:
Configuration
Driver Information
Reset Status Counters
Server Status
Configuration
Value
Description
Connection Timeout
This is the connection timeout, as set on the
ProSoft Gateway Configuration window by the
user. This is in seconds. The default value is 60.
MBAP Ports
This is the No of MBAP Server value as set on
the ProSoft Gateway Configuration window by
the user. The default value is 20. Most Modbus
devices use MBAP
MNET Ports
This is the No of MBAP Server value as set on
the ProSoft Gateway Configuration window by
the user. The default value is 20. Most Modbus
devices use MBAP
Driver Information
This displays the version# of the MNET driver in the ProSoft gateway.
Reset Status Counters
The purpose of this item is to cause a reset action in the MNET driver. When you
click this, you will see a Response field with the default value of OK. Do this
when you would like to reset the counters shown on the Server Status diagnostic
window.